FULLTEST 3
EN - 36
Where:
T ... Trip out time according to the characteristic and nominal current of used protection device
K ... See the table below
Material / Coating PVC Natural / Butyl rubber EPR/XLPE
Cu (Copper) K = 115 K = 135 K = 143
Al (Aluminium) K = 76 K = 87 K = 94
N ... Number of conductors
S ... Cross section of a conductor
For calculation of short-circuit current ISC nominal voltage Un of mains installation is needed, so it must
be selected in prior to the measurements.
How to select the nominal voltage Un:
Press the MENU SETUP NOMINAL VOL. touch-screen keys and select 230 V or 240 V. See the
chapter “NOMINAL VOLTAGE menu”.
5.6.4. LOOP MEASUREMENT
Measured quantities and display ranges:
Loop impedance LOOPL/L 0 200
Loop impedance LOOPL/N 0 200
Loop impedance LOOPL/PE 0 200
Loop impedance LOOPL/L (IMP57) 0 2
Loop impedance LOOPL/N (IMP57) 0 2
Loop impedance LOOPL/PE (IMP57) 0 2
Mains voltage UL/L 173 460 V
Mains voltage UL/N or UL/PE 100 265 V
Short circuit current ISC 0.05 46.00 kA
Input requirements:
Mains voltage UL/L (READY condition) 173 460 V AC
Mains voltage U
L/N or UL/PE (READY condition) 100 265 V AC
1) Select LOOP measurement by pressing the FUNC hard key first.
2) Check selected measurement mode (LOOP L/N, LOOP L/L, LOOP L/PE, IMP57 L/N, IMP57 L/L or
IMP57 L/PE) and modify it if needed by pressing the MODE (5) touch-screen key first.
3) Check selected limit mode (STD, kA, I
2
t, TRIP CURR. or Ut) and modify it if needed after pressing
the LIMIT (6) touch-screen key.
4) Check other parameters (they depend on selected limit mode) like type of protection, nominal
current, wire material etc. and modify them if needed by pressing appropriate parameter touch-
screen key first.
5) Select measurement screen by pressing the
(4) touch-screen key and check all settings again.
6) Connect the test leads according to one of the figures below.