2. GENERAL DESCRIPTION
Dear Customer, the instrument you have purchased, whether used according to the instructions given in
this manual, will grant you accurate and reliable measurements. Thanks to a development of newest
conception assuring overvoltage category III you will enjoy the highest safety.
The Machinery Tester FULLTEST 3 is a measurement instrument used for final inspection of electrical
equipment of machines, control cabinets, switchgears as well as other devices complying with
IEC/EN60204-1 and IEC/EN61439-1 standards.
2.1. WORKING
The instrument can carry out the following tests, further to the regulations listed below:
Continuity of protective conductor
- 2-wire or 4-wire measurement method.
- Compensation of test leads in case of 2-wire measurement.
- Open-circuit test voltage 6 V approx.
- Test current 200 mA and 25 A.
- Limit value adjustable, visual and acoustic warning in case of exceeded
value.
EN61557-4
EN61439-1-§10.5.2
EN60204-1-§18.2.2
EN60598-1
EN60335-1-§27.5
EN60335-1-§A.1
EN50106
EN60950
CEI 64-8/7-CEI64/13
Insulation resistance
- Test voltage 100 V, 250 V, 500 V and 1000 V DC.
- MAN (manual) mode.
- TIMER mode.
- AUTO mode.
- Limit value adjustable, visual and acoustic warning in case of exceeded
value.
EN61557-2
CEI64-8
CEI23-51
CEI64-8/7-CEI64/13
EN61439-1-§11.9
EN60204-1
EN60598-1
Dielectric test
- Adjustable test voltage 250 V up to 5100 V AC.
- Trip out current adjustable 1 110 mA, visual and acoustic warning in
case of exceeded limit value.
- Display and trip out based on real or apparent current.
- MANUAL mode.
- RAMP mode (predefined automatic rising of test voltage).
- BURN mode.
- Protection against unauthorised use (safety measure).
- Red warning lamp connector (safety measure).
- Safety input connector (safety measure).
EN61439-1-§9.1
EN60204-1-§18.4
EN60598-1
EN60335-1-§13.3