MACROTEST 5035
EN - 13
4.1.3.1. Mode "AUTO"
At the end of the test, if the average
resistance value Ravg results to be
lower than 5Ω the instrument emits a
double sound signal indicating the
positive outcome of the test and
displays one screen similar to the
screen alongside.
CAL LOWΩ
1.07 Ω
219 mA
AUTO
SAVING: The test can be stored pressing the SAVE key twice
(according to paragraph 5.1).
4.1.3.2. Mode "R+TIMER" or “R-TIMER"
If during the test a resistance value
R+Timer or R–Timer lower than 5Ω
was detected, the instrument (after the
set time has elapsed) emits a double
sound signal indicating the positive
outcome of the test displays one screen
similar to the screen alongside.
CAL LOWΩ
1.08 Ω
219 mA 5 s
R+
R-
IMER
SAVING: The test can be stored pressing the SAVE key twice
(according to paragraph 5.1).
4.1.4. Anomalous cases during "AUTO", "R+TIMER", "R-TIMER" tests
In case a value of Ravg or R+ or R-
higher than or equal to 5Ω but lower
than 99.9Ω was detected, at the end of
the test the instrument emits a long
sound signal and displays one screen
similar to the screen alongside.
CAL LOWΩ
o 5.75 Ω
216 mA 5 s
AUTO
In AUTO mode, if a Ravg or R+ or R-
higher than 99.9Ω was detected, at
the end of the test the instrument emits
a long sound signal and displays the
screen alongside.
CAL LOWΩ
o> 99.9 Ω
- - - mA
AUTO
Average test
current value
Iavg.
Average
resistance value
Ravg.
Value of the test
current I+ or I-.
ATTENTION: value of R
hi
her than 5
99.9Ω is the
maximum value
which can be
measured in the
LOWΩ AUTO or
R+ or R-mode.
The symbols R+ or R- are displayed.
AUTO mode.
ATTENTION: value of R
avg
or R+ or R- is too
hi
h.
Duration time of
the test.
Only in case the
mode R+TIMER
or R-TIMER was
selected.
SAVE
SAVE
Text and images you copy will automatically show hereText and images you copy will automatically show here